Difference between revisions of "Ibmet"

From IARC 207 Wiki
Jump to navigation Jump to search
imported>Ken
 
imported>Ken
Line 6: Line 6:
  
 
== 15 June 2007, Ken I., Doug K. ==
 
== 15 June 2007, Ken I., Doug K. ==
 
+
* fixed 10m RMYoung wiring, details follow:
 +
=== RMYoung to logger & multiplexer wiring details ===
 
* reconnected RMYoung wiring at sensor wiring box to nominal:
 
* reconnected RMYoung wiring at sensor wiring box to nominal:
 
** WS SIG -- RED -- 6
 
** WS SIG -- RED -- 6

Revision as of 11:39, 3 July 2007

Imnavait B-site met

site TODO list

  • record as-built wiring of soil sensors
  • Flex conduit as needed

site logs

15 June 2007, Ken I., Doug K.

  • fixed 10m RMYoung wiring, details follow:

RMYoung to logger & multiplexer wiring details

  • reconnected RMYoung wiring at sensor wiring box to nominal:
    • WS SIG -- RED -- 6
    • WS REF -- BLK -- 2
    • WD EX -- BLU -- 5
    • WD SIG -- GRN -- 4
    • WD REF -- WHT -- 3
    • DRAIN -- CLR -- 1
  • used spare piece of 05103-CSI cable at logger-shack end:
    • per program listing with timestamp 07jun07 02:35:43
    • WS is on C7
    • WD on SE3 (which is multiplexer)
  • wiring from logger to multiplexer:
    • SE3 -- CLR -- COM H1
    • SE4 -- BLK -- COM L1
    • AG -- BLK -- COM L2
    • E2 -- RED -- COM H2
  • connected 10m WS to P1 & G via wiring board terminal blocks, at lower left, left to right, from multiplexer to sensor on tower:
    • empty
    • empty
    • mplx 7L2 -- BLK -- WHT to sensor
    • mplx 7H1 -- BLK -- GRN
    • mplx 7H2 -- RED -- BLU
    • CR10X P1 -- RED
    • CR10X G -- BLK
  • spliced sensor-to-4C cable at either end:
    • WHT -- WHT cable 1
    • GRN -- GRN cable 1
    • BLU -- RED cable 1
    • RED -- RED cable 2
    • BLK -- BLK cable 2