Difference between revisions of "Ibmet"

From IARC 207 Wiki
Jump to navigation Jump to search
Line 4: Line 4:
  
 
=site logs=
 
=site logs=
 +
 +
== 04 Sept 2007, Ken I. ==
 +
* rewired new logger box
 +
* moved ant to tower
 +
* pulled old cables, conduit
 +
* left radio set and yagi on old logger at shack, but radio is DEAD
 +
* installed spare DGR: 906-6035
 +
* tested conn to UK rep
 +
* set to slave/rep mode 4, 9600 baud
 +
  
 
== 16 July 2007, Ken I. ==
 
== 16 July 2007, Ken I. ==

Revision as of 11:20, 6 June 2008

Imnavait B-site met

site TODO list

  • record as-built wiring of soil sensors
  • Flex conduit as needed

site logs

04 Sept 2007, Ken I.

  • rewired new logger box
  • moved ant to tower
  • pulled old cables, conduit
  • left radio set and yagi on old logger at shack, but radio is DEAD
  • installed spare DGR: 906-6035
  • tested conn to UK rep
  • set to slave/rep mode 4, 9600 baud


16 July 2007, Ken I.

  • serviced evaporation pan, at 0925 AKST
  • water level too low for gauge
  • w/ hook gage set at 1.00, approx. 2.9 cm down to water level from the hook point
  • added 2 jugs, or 14 gal (52 L)
  • hook gage read at 2.7258

15 June 2007, Ken I., Doug K.

  • fixed 10m RMYoung wiring, details follow:
    • reconnected RMYoung wiring at sensor wiring box to nominal:
      • WS SIG -- RED -- 6
      • WS REF -- BLK -- 2
      • WD EX -- BLU -- 5
      • WD SIG -- GRN -- 4
      • WD REF -- WHT -- 3
      • DRAIN -- CLR -- 1
    • used spare piece of 05103-CSI cable at logger-shack end:
      • per program listing with timestamp 07jun07 02:35:43
      • WS is on C7
      • WD on SE3 (which is multiplexer)
    • wiring from logger to multiplexer:
      • SE3 -- CLR -- COM H1
      • SE4 -- BLK -- COM L1
      • AG -- BLK -- COM L2
      • E2 -- RED -- COM H2
    • connected 10m WS to P1 & G via wiring board terminal blocks, at lower left, left to right, from multiplexer to sensor on tower:
      • empty
      • empty
      • mplx 7L2 -- BLK -- WHT to sensor
      • mplx 7H1 -- BLK -- GRN
      • mplx 7H2 -- RED -- BLU
      • CR10X P1 -- RED
      • CR10X G -- BLK
    • spliced sensor-to-4C cable at either end:
      • WHT -- WHT cable 1
      • GRN -- GRN cable 1
      • BLU -- RED cable 1
      • RED -- RED cable 2
      • BLK -- BLK cable 2