Difference between revisions of "NGEE Barrow Intensive Sites Initial Wiring"

From IARC 207 Wiki
Jump to navigation Jump to search
Line 1: Line 1:
Since the site will only be partially installed in September this will be the initial setup.
+
General Wiring 2013
<pre>
+
(Some minor differences like 3 SR50As at site C)
'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''
 
'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''
 
'''  FALL SENSOR LIST  '''''''''''''''''''''''''''''''''''
 
'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''
 
'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''
 
' 3 -- HFP01 Heat Flux Plates
 
' 9 -- Vitel HydraProbe II Probes
 
' 9 -- East30 Sensors Thermal Conductivity Probes [Not yet added]
 
' 5 -- 16 point thermistor strings
 
' 9 -- thermistors to be installed adjacent to the soil moisture probes
 
' 1 -- 5 point shallow borehole
 
' 1 -- 107 Air Temperature
 
' 1 or 2 -- SR50A Snow Depth
 
' 3 -- HFP01 Heat Flux Sensors
 
  
'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''
+
' SE1  -- CNR4 SW In HI
'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''
+
' SE2  -- CNR4 SW In LO
''' LOGGER WIRING  ''''''''''''''''''''''''''''''''''''''
+
' SE3  -- CNR4 SW OUT HI
'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''
+
' SE4  -- CNR4 SW OUT LO
'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''
+
' SE5  -- CNR4 LW IN HI
 +
' SE6  -- CNR4 LW IN LO
 +
' SE7  -- CNR4 Dome Temperature Signal
 +
' SE8  -- 107 Probe Signal (Red Wire)
 +
' SE9  -- CNR4 LW OUT HI
 +
' SE10 -- CNR4 LW OUT LO
 +
' SE11 -- AM16/32B #3 COM ODD HI
 +
' SE12 -- AM16/32B #3 COM ODD LO
 +
' SE13 -- AM16/32B #1 COM ODD HI, Precision Resistor to VX2
 +
  ' SE14 -- AM16/32B #1 COM ODD LO, Precision Resistor to VX2
 +
' SE15 -- AM16/32B #2 COM ODD HI, Precision Resistor to VX3
 +
' SE16 -- AM16/32B #2 COM ODD LO, Precision Resistor to VX3
  
' SE1  -- HFP01 #1 HI (White Wire)
+
  ' VX1 -- 107 Probe Excitation (Black Wire); **CNR4 LW Dome Temperature Excitation**, **RM Young WD Excite**
' SE2  -- HFP01 #1 LO (Green Wire)
+
  ' VX2 -- Precision resistors to Mux 2 COM ODD HI, SE1, COM ODD LO, SE2
' SE3  -- HFP01 #2 HI (White Wire)
+
' VX3 -- Precision resistors to Mux 3 COM ODD HI, SE1, COM ODD LO, SE2,
' SE4  -- HFP01 #2 LO (Green Wire)
 
' SE5  -- HFP01 #3 HI (White Wire)
 
' SE6  -- HFP01 #3 LO (Green Wire)
 
' SE7 --
 
' SE8  -- 107 Probe Signal (Red Wire)
 
' SE9 --
 
' SE10 --
 
' SE11 --
 
' SE12 --
 
' SE13 -- AM16/32B #1 COM ODD HI, Precision Resistor to VX2
 
' SE14 -- AM16/32B #1 COM ODD LO, Precision Resistor to VX2
 
' SE15 -- AM16/32B #2 COM ODD HI, Precision Resistor to VX3
 
' SE16 -- AM16/32B #2 COM ODD LO, Precision Resistor to VX3
 
  
' VX1 -- 107 Probe Excitation (Black Wire)
+
' P1 -- MetOne 1m WS+
' VX2 -- Precision resistors to Mux 2 COM ODD HI, SE1, COM ODD LO, SE2
+
' P2 -- MetOne 3.5m WS+
' VX3 -- Precision resistors to Mux 3 COM ODD HI, SE1, COM ODD LO, SE2
 
  
' P1 --  
+
' C1 -- SDM IO C1
' P2 --  
+
' C2 -- SDM IO C2
 +
' C3 -- SDM IO C3
 +
' C4 -- AM16/32B #1, 2, & 3 -- CLK
 +
' C5 -- SDI 12 Devices Part 1 (6 Vitel Probes ) (Blue Wire)
 +
' C6 -- Vitel Probe CONTROL (Run to SW12V Control for Vitel Probes)
 +
' C7 -- SDI 12 Devices Part 2 (2 SR50A ) (Green Wire)
 +
' C8 -- TE525M Signal
 +
' SW12V -- Radio Power
  
' C1 --
+
' Wiring that will need to be moved / extended to the SDM Interface:
' C2 -- AM16/32B #1 -- RES
+
' C2 -- AM16/32B #1 -- RES
' C3 -- AM16/32B #2 -- RES
+
' C3 -- AM16/32B #2 -- RES
' C4 -- AM16/32B #1 & 2 -- CLK
+
' C8 -- Thermal Conductivity Control
' C5 -- SDI 12 Devices Part 1 (9 Vitel Probes )
 
' C6 -- Vitel Probe CONTROL
 
' C7 -- SDI 12 Devices Part 2 (1 or 2 SR50A ) (Green Wire)
 
' C8 -- Thermal Conductivity Control
 
' SW12V -- Radio Power
 
  
' Signal Ground -- HFP01 Shields (Clear Wire), 107 Probe SG (Purple Wire), SR50A  
+
' Signal Ground -- HFP01 Shields (Clear Wire), 107 Probe SG (Purple Wire), SR50A  
'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''
 
'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''
 
''  Sensor Wiring  ''''''''''''''''''''''''''''''''''''''
 
'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''
 
'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''
 
' 107 Probe
 
' Black Wire -- CR1000 VX1
 
' Red Wire  -- CR1000 SE8
 
' Purple Wire -- CR1000 Signal Ground
 
' Clear Wire -- CR1000 Signal Ground
 
  
' HFP01
+
' SDM Interface Wiring:
' White Wire -- CR1000 SE1, 3, or 5
+
' 1 -- AM16/32B #1 RES
' Green Wire -- CR1000 SE2, 4, or 6
+
' 2 -- AM16/32B #2 RES
' Clear Wire -- CR1000 Signal Ground
+
' 3 -- AM16/32B #3 RES
 
+
' 4 -- Thermal Conductivity Control
' SR50A
+
' 5 -- HMP155 Control
' Black Wire -- CR1000 Power Ground
+
' 6 -- CNR4 Heater/Fan Control
' Red Wire -- CR1000 +12V
 
' Green Wire -- CR1000 C7
 
' White Wire -- CR1000 Ground
 
' Clear Wire -- CR1000 Ground
 
 
 
' HydraProbe II
 
' Red Wire -- CR1000 +12V
 
' Black Wire -- CR1000 Ground
 
' Blue Wire -- CR1000 C5
 
</pre>
 

Revision as of 18:32, 21 April 2013

General Wiring 2013 (Some minor differences like 3 SR50As at site C)

' SE1  -- CNR4 SW In HI
' SE2  -- CNR4 SW In LO
' SE3  -- CNR4 SW OUT HI
' SE4  -- CNR4 SW OUT LO
' SE5  -- CNR4 LW IN HI
' SE6  -- CNR4 LW IN LO
' SE7  -- CNR4 Dome Temperature Signal
' SE8  -- 107 Probe Signal (Red Wire)
' SE9  -- CNR4 LW OUT HI
' SE10 -- CNR4 LW OUT LO
' SE11 -- AM16/32B #3 COM ODD HI
' SE12 -- AM16/32B #3 COM ODD LO
' SE13 -- AM16/32B #1 COM ODD HI, Precision Resistor to VX2
' SE14 -- AM16/32B #1 COM ODD LO, Precision Resistor to VX2
' SE15 -- AM16/32B #2 COM ODD HI, Precision Resistor to VX3
' SE16 -- AM16/32B #2 COM ODD LO, Precision Resistor to VX3
' VX1 -- 107 Probe Excitation (Black Wire); **CNR4 LW Dome Temperature Excitation**, **RM Young WD Excite**
' VX2 -- Precision resistors to Mux 2 COM ODD HI, SE1, COM ODD LO, SE2
' VX3 -- Precision resistors to Mux 3 COM ODD HI, SE1, COM ODD LO, SE2, 
' P1 -- MetOne 1m WS+
' P2 -- MetOne 3.5m WS+
' C1 -- SDM IO C1
' C2 -- SDM IO C2
' C3 -- SDM IO C3
' C4 -- AM16/32B #1, 2, & 3 -- CLK
' C5 -- SDI 12 Devices Part 1 (6 Vitel Probes ) (Blue Wire)
' C6 -- Vitel Probe CONTROL (Run to SW12V Control for Vitel Probes)
' C7 -- SDI 12 Devices Part 2 (2 SR50A ) (Green Wire)
' C8 -- TE525M Signal
' SW12V -- Radio Power
' Wiring that will need to be moved / extended to the SDM Interface:
' C2 -- AM16/32B #1 -- RES
' C3 -- AM16/32B #2 -- RES
' C8 -- Thermal Conductivity Control
' Signal Ground -- HFP01 Shields (Clear Wire), 107 Probe SG (Purple Wire), SR50A 
' SDM Interface Wiring:
' 1 -- AM16/32B #1 RES
' 2 -- AM16/32B #2 RES
' 3 -- AM16/32B #3 RES
' 4 -- Thermal Conductivity Control
' 5 -- HMP155 Control
' 6 -- CNR4 Heater/Fan Control