Line 14: | Line 14: | ||
*** WD REF -- WHT -- 3 | *** WD REF -- WHT -- 3 | ||
*** DRAIN -- CLR -- 1 | *** DRAIN -- CLR -- 1 | ||
− | |||
** used spare piece of 05103-CSI cable at logger-shack end: | ** used spare piece of 05103-CSI cable at logger-shack end: | ||
*** per program listing with timestamp 07jun07 02:35:43 | *** per program listing with timestamp 07jun07 02:35:43 | ||
*** WS is on C7 | *** WS is on C7 | ||
*** WD on SE3 (which is multiplexer) | *** WD on SE3 (which is multiplexer) | ||
− | |||
** wiring from logger to multiplexer: | ** wiring from logger to multiplexer: | ||
*** SE3 -- CLR -- COM H1 | *** SE3 -- CLR -- COM H1 | ||
Line 25: | Line 23: | ||
*** AG -- BLK -- COM L2 | *** AG -- BLK -- COM L2 | ||
*** E2 -- RED -- COM H2 | *** E2 -- RED -- COM H2 | ||
− | |||
** connected 10m WS to P1 & G via wiring board terminal blocks, at lower left, left to right, from multiplexer to sensor on tower: | ** connected 10m WS to P1 & G via wiring board terminal blocks, at lower left, left to right, from multiplexer to sensor on tower: | ||
*** empty | *** empty | ||
Line 34: | Line 31: | ||
*** CR10X P1 -- RED | *** CR10X P1 -- RED | ||
*** CR10X G -- BLK | *** CR10X G -- BLK | ||
− | |||
** spliced sensor-to-4C cable at either end: | ** spliced sensor-to-4C cable at either end: | ||
*** WHT -- WHT cable 1 | *** WHT -- WHT cable 1 |
Revision as of 11:42, 3 July 2007
site TODO list
- record as-built wiring of soil sensors
- Flex conduit as needed
site logs
15 June 2007, Ken I., Doug K.
- fixed 10m RMYoung wiring, details follow:
- reconnected RMYoung wiring at sensor wiring box to nominal:
- WS SIG -- RED -- 6
- WS REF -- BLK -- 2
- WD EX -- BLU -- 5
- WD SIG -- GRN -- 4
- WD REF -- WHT -- 3
- DRAIN -- CLR -- 1
- used spare piece of 05103-CSI cable at logger-shack end:
- per program listing with timestamp 07jun07 02:35:43
- WS is on C7
- WD on SE3 (which is multiplexer)
- wiring from logger to multiplexer:
- SE3 -- CLR -- COM H1
- SE4 -- BLK -- COM L1
- AG -- BLK -- COM L2
- E2 -- RED -- COM H2
- connected 10m WS to P1 & G via wiring board terminal blocks, at lower left, left to right, from multiplexer to sensor on tower:
- empty
- empty
- mplx 7L2 -- BLK -- WHT to sensor
- mplx 7H1 -- BLK -- GRN
- mplx 7H2 -- RED -- BLU
- CR10X P1 -- RED
- CR10X G -- BLK
- spliced sensor-to-4C cable at either end:
- WHT -- WHT cable 1
- GRN -- GRN cable 1
- BLU -- RED cable 1
- RED -- RED cable 2
- BLK -- BLK cable 2
- reconnected RMYoung wiring at sensor wiring box to nominal: